Transfer the UPS into Maintenance Bypass Operation
Note: If shutdown via the display is disabled, then you cannot perform this procedure and
the message: Command not allowed, UPS congured to never shutdown appears. If
you want to enable shutdown via the display, this is done by an Field Service Engineer
via the UPSTuner.
1. Select UPS and press ENTER.
→ UPS Alarms
Power Dist Log
Switch Gear Admin
Environment Help
2. Select UPS Power Control and press ENTER.
→ UPS Power Control
UPS Status
UPS Tests & Diags
UPS Configuration
3. Select UPS into Bypass and press ENTER.
Turn UPS Off
Reboot UPS
→ UPS into Bypass
UPS to Sleep
4. Select Yes, Into Bypass and press ENTER.
Confirm:
UPS into Bypass?
NO, ABORT
→ YES, Into Bypass
5. Wait for the transfer to complete.
Putting UPS into
Bypass, please
wait....
6. Conrm that the transfer to bypass is complete.
Note: The H3 LED next to the Q3
switch will turn on, indicating that it
is ok to operate the Q3 switch.
UPS is now in
Bypass.
Press any key....
7. Set the Q3 switch to the ON position.
Note: The H2 LED beside the Q2
switch will turn on, indicating that it
is ok to operate the Q2 switch.
8. Set the Q2 switch to the OFF position.
14
Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation