of 32
 
DeviceNet Network Scanner DVPDNET-SL
DVP-PLC Operation Manual
15
Item Function Default
DIDO Output
Points (Y)
The digital output points shall be 8’s multiple. The number will
be regarded as 8 when it is less than 8 and regarded as 16
when it is bigger than 8 but less than 16.
N/A
AIAO Module
Number
The number of special I/O modules connected to RTU-DNET.
Range: 0 ~ 8
N/A
Diagnostic
Intervel Time
The interval when RTU-DNET executes diagnosis. Range:
1~ 65 secs
5 (sec)
IO Module
Offine Treatment
How RTU-DNET will react when the special I/O module
connected to it is offline. You can choose “Ignored”, "Alarm”
or “stop DeviceNet IO".
Alarm
IO Module
Error Treatment
How RTU-DNET will react when it detects errors. You can
choose “Ignored”, “Alarm” or “Stop DeviceNet IO”.
Alarm
Add control word
and status word to
IO data
For you to decide whether to add control word and status
word to I/O data. When you choose not to do it, the I/O data
in RTU-DNET and DeviceNet master will not include control
word and status word. If you choose to add them in, the I/O
data in RTU-DNET and DeviceNet master will include control
word and status word.
Not to add
(13) Confirm all the configurations are correct and click on “Download” to download the configurations to
RTU-DNET. After the download is completed, click on “OK”.
(14) After the configuration o f RTU-DNET is completed, you will return to the main page.
(15) Double click on VFD-B Drives (node 03), and the “Node Configuration…” dialog box will appear.